Unitile Chip Board (Non-Encapsulated) panels constructed around a high density E1 grade chipboard core. The system fully complies with the Euro Class requirement of EN 12825. The base and the top surface of the core is factory bonded using an appropriate combination of surface finishes such as Aluminum, Galvanized Iron sheet, High Pressure Laminate etc. 

DIMENSIONS: 600 mm x 600 mm | 600 mm x 800 mm

PANEL THICKNESS: 35 mm | 38 mm

TOP: Galvanized Iron Sheet / HPL / PVC

BOTTOM: Galvanizes Iron Sheet / Aluminium foil

CORE: High density E1-grade chipboard

APPLICATION: Open office, Data center, Control room, Casino, Co-working, Education

features

Data Center Accessories Unitile

High strength to weight performance

Data Center Accessories Unitile

Unique inbuilt stringer design

Data Center Accessories Unitile

Environment-friendly core system

Data Center Accessories Unitile

Precise floor levelling and positive alignment

Data Center Accessories Unitile

Enhanced electrical continuity

Data Center Accessories Unitile

Good acoustical property

system selection guide

System Selection Guide
  • Structural Performance as per BSEN 12825
  • Classification
  • Class A
  • Class B
  • Class C
  • Deflection
  • 2.5 mm
  • 3.0 mm
  • 4.0 mm
  • 35 mm
  • Concentrated Load kgs (KN)
  • 530 / 5.19
  • 600 / 5.88
  • 740 / 7.25
  • 38 mm
  • Concentrated Load kgs (KN)
  • 660 / 6.47
  • 690 / 6.76
  • 840 / 8.23
*Contact us for detailed specifiations of design.
System Selection Guide 2
  • Structural Performance as per BSEN 12825
  • Ultimate Concentrated Load
  • Uniformly Distributed Load / Sq mtr
  • Pedestal Axial Load Test
  • Technical Specifications
  • 35 mm
  • 1600 Kgs / 15.68 KN
  • 2300 Kgs / Sq. mtr
  • 22 KN (2245 kgs) Axial Load per pedestal
  • Download
  • 38 mm
  • 1650 Kgs / 16.17 KN
  • 2350 Kgs / Sq. mtr
  • 22 KN (2245 kgs) Axial Load per pedestal
  • Download
* Contact us for detailed specifiations of the product design.

    types of understructure support system

  • Edge Rigid Grid System

    Edge Rigid Grid System

    Edge support under-structure provides maximum floor stability. It reduces all lateral movements and also ensures integrity of the floor on removal of panels for access to services in the sub-floor. Stringers are mechanically fastened to the pedestal head and panels are then placed on the grid formed. This system is ideal for high finished floor heights.

    • FINISHED FLOOR HEIGHT:
    • Minimum: 150 mm
      Maximum: 2000 mm
  • Drawings

  • certificates

    • UCB 35 - 25 Square inch test-MOB PF

      Download
    • UCB 35 - 25 Square inch-safety factor-MOB PF

      Download
    • UCB 35 VG - 25 Square inch test-MOB PF

      Download
    • UCB 35 VG - 25 Square inch-safety factor-MOB PF

      Download
    • UCB 35 VG - UDL safety factor-MOB PF

      Download
    • UCB 35 VG - UDL test-MOB PF